RVS-DN
Which soft starter is considered as the most reliable soft starter in todays' Industrial and Marine markets ?
The RVS-DN is a severe duty, Full Featured, Motor Protection enhanced, Microprocessor-Based, for Motors 4-3500A, 4-3000KW, 208-690V.
For 1000V and 1200V click << RVS-DN for 1000V and 1200V
For 2300V to 15000V click << HRVS-DN Medium Voltage Soft Starter >>.0
View these soft starters in demanding environmental conditions check out our Naval, Marine, Industial, Oil and Gas examples of Solcon soft-starters in a variety of applications
Advantages at a Glance
Eliminates high inrush current and damaging mechanical shock
Third generation microprocessor circuitry
Heavy duty design: 50°C ambient temperature
Soft, stepless acceleration & deceleration
Power factor capacitors can be connected directly to the upstream contactor
Unique starting & stopping characteristics (special characteristics for Ex motors)
Unique features such as: Pump Control Program, Dual Adjustment, Slow Speed with Electronic Reversing, Energy Save, etc.
Torque and current starting & stopping characteristics
Sophisticated motor protection package with Enhanced features
User friendly, easy installation and operation
RS485 Communication with MODBUS, PROFIBUS or MODBUS/TCP protocols (others available on request)
Wide 45-65Hz Auto-tracking frequency range combining special software with unique hardware arrangement allowing starting and stopping while the frequency variates (designed for Marine, Offshore and Generators operating under continuous frequency variation
Possibility to operate without bypass contactor at 50°C up to 820A
|
RVS-DN Protection Features
- Start & start inhibit with time delays
- Long start time (Stall protection)
- Electronic shear-pin (Jam) with adjustable curves and delay
- Electronic overload with selectable curves
- Under current with programmable auto reset
- Phase loss
- Phase sequence and Under/Over frequency
- Under/Over voltage with programmable auto reset
- Load loss (indentifying broken drive belt, lack of water in a well, etc.)
- External fault
- Shorted SCR
- Starter over temperature protection
- Motor insulation test (option)
- Motor thermistor (option)
- Analogue Ouput (option)
- When using "Preparation for Bypass" all protective functions remain active
|
|
|
RVS-DN Control
- All inputs & outputs are isolated
- Three C/O output relays
- Thermistor input
- Analogue output
- Communication RS 485 with MODBUS RTU or MODBUS Plus protocols
- User friendly keypad interface allowing precise settings
- Bright LEDs for immediate visual interface
- Interactive and informative 4 language LCD for easy trouble shooting
- Statistical data
- Motor insulation protection
- Hardware and software integration to allow starting from diesel-generator
RVSDN Construction
- Heavy duty fully rated design (ambient 50°C)
- Compact, light weight
- Cost efficient plug-in control module, identical for sizes B-G
- Preparation for bypass contactor (option), maintaining protection after the bypass contactor is closed
RVS-DN with Motor Protection Features Typical Applications
- Pumps (Water utilities, Industry)
- Compressors
- Conveyors & monorails
- Mixers & Agitators
- Fans & Centrifuges
- Hydraulic pumps
- Starting from weak Mains supply
- Marine (Thrusters, pumps, fans, refrigeration, compressors, etc..)
|
| RVS-DN Soft Starter |
| Starter Type |
Motor KW |
Motor HP |
Starter Size |
Dimensions (mm) & Weight |
|
V~ +10% : -15% |
V~ +10% : -15% |
|
230V |
380-440V |
500V |
690V |
230V |
460V |
575V |
A-G |
W |
H |
D |
Kg |
|
RVS-DN 8 |
2.2 |
4 |
5.5 |
7.5 |
3 |
5 |
7.5 |
A |
153 |
310 |
170 |
5 |
|
RVS-DN 17 |
4 |
7.5 |
11 |
15 |
5 |
10 |
15 |
153 |
310 |
170 |
5 |
|
RVS-DN 31 |
7.5 |
15 |
16.5 |
22 |
10 |
20 |
30 |
153 |
310 |
217 |
7 |
|
RVS-DN 44 |
11 |
22 |
30 |
37 |
15 |
30 |
40 |
153 |
310 |
217 |
8 |
|
RVS-DN 58 |
15 |
30 |
37 |
45 |
20 |
40 |
50 |
153 |
310 |
217 |
8 |
|
RVS-DN 72 |
18.5 |
37 |
45 |
55 |
25 |
50 |
60 |
153 |
310 |
217 |
8 |
|
RVS-DN 85 |
22 |
45 |
55 |
65 |
30 |
60 |
75 |
B |
274 |
370 |
279 |
15 |
|
RVS-DN 105 |
30 |
55 |
75 |
90 |
40 |
75 |
100 |
274 |
370 |
279 |
15 |
|
RVS-DN 145 |
37 |
75 |
90 |
132 |
50 |
100 |
125 |
274 |
370 |
279 |
15 |
|
RVS-DN 170 |
45 |
90 |
110 |
160 |
60 |
125 |
150 |
274 |
370 |
279 |
15 |
|
RVS-DN 210 |
55 |
110 |
132 |
185 |
75 |
150 |
200 |
C |
590 |
500 |
275 |
45 |
|
RVS-DN 310 |
90 |
160 |
220 |
250 |
100 |
200 |
300 |
590 |
500 |
275 |
45 |
|
RVS-DN 390 |
110 |
200 |
250 |
315 |
125 |
250 |
350 |
590 |
500 |
275 |
45 |
|
RVS-DN 460 |
132 |
250 |
315 |
450 |
150 |
300 |
400 |
|
623 |
660 |
290 |
65 |
|
RVS-DN 580 |
160 |
315 |
400 |
500 |
200 |
400 |
500 |
|
623 |
660 |
290 |
65 |
|
RVS-DN 820 |
250 |
450 |
600 |
750 |
300 |
600 |
700 |
|
623 |
660 |
290 |
65 |
|
RVS-DN 950 |
295 |
500 |
670 |
925 |
400 |
815 |
1030 |
D |
623 |
660 |
290 |
83.5 |
|
RVS-DN 1100 |
355 |
630 |
800 |
1000 |
400 |
800 |
1000 |
|
723 |
1100 |
370 |
170 |
|
RVS-DN 1400 |
400 |
800 |
900 |
1300 |
500 |
1000 |
1250 |
|
723 |
1100 |
370 |
170 |
|
RVS-DN 1800 |
560 |
950 |
1250 |
1500 |
600 |
1250 |
1500 |
E |
723 |
1100 |
370 |
170 |
|
RVS-DN 2150 |
NA |
1250 |
1500 |
2000 |
700 |
1500 |
2000 |
F |
750 |
1300 |
392 |
235 |
|
RVS-DN 2400 |
NA |
1400 |
1750 |
2250 |
800 |
1750 |
2250 |
|
900 |
1300 |
360 |
350 |
|
RVS-DN 2700 |
NA |
1550 |
2000 |
2500 |
900 |
2000 |
2500 |
G |
900 |
1300 |
360 |
350 | |
* Type test (DNV is type approved as of April 2006)
Notes:
RVS-DN 8 through RVS-DN 820 are UL & cUL Approved
RVS-DN 1100 and above are designed to meet UL & cUL requirements
Contact us for RVS-DN 210, 310, 390, 460, 580, 820 & 950 Slim version (Narrow)
Select the starter according to motor's Full Load Ampere (FLA) - as indicated on its nameplate (even if the motor is not fully loaded)
The selection table above, concerns standard, 1500 R.P.M. 50Hz, three-phase asynchronous motors. These values are given for guidance and may vary according to individual motor manufacturers (as well as number of poles)
It is the user’s responsibility to verify that motor’s FLA does not exceed Starter’s FLC